Error message
C030 Alarm with supply voltages CC%d
Cause of error
- The internal supply voltages of the CC are outside of the specified range. Please pay attention to the diagnostic message "0xC038 voltage monitoring"!
Error correction
- Check the supply voltages on the CC:
- Check the wiring of X69
- Cable length at X69 within specification?
- Exchange the cable on X69
- Exchange the hardware
- Inform your service agency