380070 |
Profibus DP: no input slot available for base address %1 (length %2) |
Parameters: |
%1 = Logical base address of the requested area %2 = Size of the area in bytes |
Definitions: |
An incorrect logical base address was specified for a digital or analog input. Either no slot has been configured for this base address or the requested area extends beyond the end of the slot. |
Reactions: |
Length=1 indicates a digital input. Length=2 indicates a analog input. - Channel not ready. - NC Start disable in this channel. |
Remedy: |
- Interface signals are set. - Alarm display. Enter correct base addresses in the machine data: For length=1: Correct machine data MN_HW_ASSIGN_DIG_FASTIN. For length=2: Correct machine data MN_HW_ASSIGN_ANA_FASTIN. NCK restart |
Program Continuation: |
If the error cannot be eliminated by this procedure, please make a note of the error text and contact the control system manufacturer. Switch control OFF - ON. |