Remedy:
Program Continuation:
Axis %1 drive %2 controlled system gain is less than or equal to zero
%1 = NC axis number %2 = Drive number
The controlled system gain in drive MD 5435: CONTROLLED_SYSTEM_GAIN is less than or equal to zero.
- NC not ready.
- The NC switches to follow-up mode.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
- Channel not ready.
Enter a valid controlled system gain in drive MD 5435: CONTROLLED_SYSTEM_GAIN (see model data calculations).
Clear alarm with the RESET key in all channels. Restart part program.
© Siemens AG 2005 All Rights Reserved