310610

Parameters:

Definitions:


Reactions:


Remedy:


Program Continuation:


Axis %1 drive %2 wrong piston position

%1 = NC axis number %2 = Drive number

The error is triggered if the actual position of the drive is negative.

Cause:

Incorrect counting direction of actual position on drive side.

Incorrect piston zero alignment.

If the drive is referenced and the offset between the piston zero (piston stop at A side) and the machine zero is entered in MD 5040, the piston position in MD 5741 can only indicate positive values (from zero to piston stroke length).

-    Mode group not ready.

-    The NC switches to follow-up mode.

-    Channel not ready.

-    NC Start disable in this channel.

-    Interface signals are set.

-    Alarm display.

-    NC Stop on alarm.

-    Channel not ready.

The counting direction for the actual position is correct on the drive side if:

1.    Pos. setpoint voltage (e.g. function generator) -> cylinder piston travels from A to B. If not: Invert the actuation signal (change MD 5476 bit 0).

2.    Cylinder piston travels from A to B -> v_act (MD 5707) > 0. If not: Invert the actual value (change MD 5011 bit 0).

Check the piston zero alignment and correct if necessary:

Set MD 5012 bit 14 and bit 15 to zero, save bootfile, reset NCK, perform a reference point approach and then align the position.

Clear alarm with the RESET key in all channels of this mode group. Restart part program.


1-2723