301705
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
Axis %1 drive %2 distance-coded scale incorrectly parameterized
%1 = NC axis number %2 = Drive number
When selecting a distance-coded scale (MD_1011.7=1) it is also necessary to configure a length measuring system (MD_1011.4=1). In addition, the MDs 1040, 1041 and 1042 must not be zero or negative.
- Mode group not ready.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
Please inform the authorized personnel/service department. Check and, if necessary, correct MDs 1011: $MD_ACTUAL_VALUE_CONFIG (actual value sensing configuration IM), 1040, 1041 and 1042.
Switch control OFF - ON.
1-2703