Axis %1 drive %2 stop B triggered
%1 = Axis number %2 = Drive number
The drive is disabled via STOP B. This blocks the pulses over the relay "AntriebJMP". Request: In monitoring cycle.
If STOP B has been triggered, this can have several reasons:
1. Safe zero speed control has responded.
2. Call after STOP F, that means an error has occurred during cross-comparison.
3. "SG-specific stop reaction" is set to STOP B and has responded.
The alarm can be reprogrammed in the MD ALARM_REACTION_CHAN_NOREADY (channel not ready).
- Mode group not ready.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
- Channel not ready.
Please inform the authorized personnel/service department. The user must check the cause and initiate the corresponding measures.
Switch control OFF - ON.