300859
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
Axis %1 drive %2 generator mode: response voltage > monitoring threshold
%1 = NC axis number %2 = Drive number
The value in MD 1631: $MD_LINK_VOLTAGE_GEN_ON (response voltage for generator axis) is greater than MD1630: $MD_LINK_VOLTAGE_MON_THRESHOLD (response threshold for DC link monitoring).
- Interface signals are set.
- Alarm display.
Please inform the authorized personnel/service department.
Modify MD 1631: $MD_LINK_VOLTAGE_GEN_ON (response voltage for generator axis) or
Modify MD 1630: $MD_LINK_VOLTAGE_MON_THRESHOLD (response threshold for DC link monitoring).
Alarm display showing cause of alarm disappears. No further operator action necessary.
1-2677