300781 |
Axis %1 drive %2 zero load current > rated current of power section |
Parameters: |
%1 = NC axis number %2 = Drive number |
Definitions: |
On the basis of its no-load current (MD 1136: $MD_MOTOR_NOLOAD_CURRENT (motor no-load current), the connected motor is too large for the power section in use (continuous thermal current MD 1108: $MD_INVERTER_MAX_THERMAL_CORR (current limit for power section). The alarm can be reprogrammed in the MD ALARM_REACTION_CHAN_NOREADY (channel not ready). |
Reactions: |
- NC not ready. - The NC switches to follow-up mode. - Channel not ready. - NC Start disable in this channel. |
Remedy: |
- Interface signals are set. - Alarm display. - NC Stop on alarm. - Channel not ready. Please inform the authorized personnel/service department. 1. Reset the drive (delete the bootfile) and repeat the startup. 2. Check the configuration and install a suitable power section for the motor. Repeat the startup. |
Program Continuation: |
Clear alarm with the RESET key in all channels. Restart part program. |