300778

Parameters:

Definitions:

Reactions:


Remedy:

Program Continuation:


Axis %1 drive %2 generator mode: converter frequency rotor position identification

%1 = NC axis number %2 = Drive number

When selecting the rotor position identification (MD1011 bit 12 or bit 13) only converter frequencies (MD1100) of 4 kHz/8 kHz are permissible.

Modify MD 1011: $MD_ACTUAL_VALUE_CONFIG (actual value sensing configuration IM)

Modify MD 1100: $MD_PWM_FREQUENCY (pulse width modulation frequency)

The alarm can be reprogrammed in the MD ALARM_REACTION_CHAN_NOREADY (channel not ready).

-    NC not ready.

-    The NC switches to follow-up mode.

-    Channel not ready.

-    NC Start disable in this channel.

-    Interface signals are set.

-    Alarm display.

-    NC Stop on alarm.

-    Channel not ready.

Please inform the authorized personnel/service department.

Change the converter frequency (MD 1100) or deselect rotor position identification (MD1011 bit 12 or bit 13).

Modify MD 1011: $MD_ACTUAL_VALUE_CONFIG (actual value sensing configuration IM)

Modify MD 1100: $MD_PWM_FREQUENCY (pulse width modulation frequency)

Clear alarm with the RESET key in all channels. Restart part program.


1-2659


© Siemens AG 2005 All Rights Reserved