300777

Parameters:

Definitions:


Reactions:


Remedy:

Program Continuation:


Axis %1 drive %2 rotor position identification current too high

%1 = NC axis number %2 = Drive number

The current set in MD1019: $MD_CURRENT_ROTORPOS_IDENT (current rotor position identification) is greater than the permissible current for the motor and the power section used.

The alarm can be reprogrammed in the MD ALARM_REACTION_CHAN_NOREADY (channel not ready).

-    NC not ready.

-    The NC switches to follow-up mode.

-    Channel not ready.

-    NC Start disable in this channel.

-    Interface signals are set.

-    Alarm display.

-    NC Stop on alarm.

-    Channel not ready.

Please inform the authorized personnel/service department. Reduce MD1019: $MD_CURRENT_ROTORPOS_IDENT (current rotor position identification).

Clear alarm with the RESET key in all channels. Restart part program.


© Siemens AG 2005 All Rights Reserved


1-2658