300767 |
Axis %1 drive %2 natural frequency > Shannon frequency |
Parameters: |
%1 = NC axis number %2 = Drive number |
Definitions: |
The natural frequency of a speed setpoint filter is greater than the Shannon sampling frequency from the sampling theorem. The alarm can be reprogrammed in the MD ALARM_REACTION_CHAN_NOREADY (channel not ready). |
Reactions: |
- NC not ready. - The NC switches to follow-up mode. - Channel not ready. - NC Start disable in this channel. |
Remedy: |
- Interface signals are set. - Alarm display. - NC Stop on alarm. - Channel not ready. Please inform the authorized personnel/service department. The natural frequency in Hz of a speed setpoint filter must be less than the reciprocal value of two speed controller cycles. Speed setpoint filter 1: MD 1520 * 0.01 * MD 1514 < 1 / ( 2 * MD 1001 * 31.25 microsec) Speed setpoint filter 2: MD 1521 * 0.01 * MD 1517 < 1 / ( 2 * MD 1001 * 31.25 microsec) Modify MD 1520: $MD_SPEED_FILTER_1_BS_FREQ (bandstop filter natural frequency speed setpoint filter 1) Modify MD 1514: $MD_SPEED_FILTER_1_SUPPR_FREQ (suppression frequency speed setpoint filter 1) 1) Modify MD 1521: $MD_SPEED_FILTER_2_BS_FREQ (bandstop filter natural frequency speed setpoint filter 2) Modify MD 1517: $MD_SPEED_FILTER_2_SUPPR_FREQ (suppression frequency speed setpoint filter 2) 2) Modify MD 1001: $MD_SPEEDCTRL_CYCLE_TIME (speed controller cycle) |
Program Continuation: |
Clear alarm with the RESET key in all channels. Restart part program. |