300766

Parameters:

Definitions:

Reactions:


Remedy:


Program Continuation:


Axis %1 drive %2 blocking frequency > Shannon frequency

%1 = NC axis number %2 = Drive number

The blocking frequency of a speed setpoint filter is greater than the Shannon sampling frequency from the sampling theorem.

-    NC not ready.

-    The NC switches to follow-up mode.

-    Channel not ready.

-    NC Start disable in this channel.

-    Interface signals are set.

-    Alarm display.

-    NC Stop on alarm.

-    Channel not ready.

Please inform the authorized personnel/service department.

Current setpoint filter:

The value in MD 1210, 1213,1216 or 1219 must be smaller than the inverse value of two current controller cycles MD 1000: $MD_CURRENTCTRL_CYCLE_TIME (current controller cycle) (1/2*MD 1000 *31.25 microsec).

Speciality with SINUMERIK 810D:

Current setpoint filters 2,3 and 4 are calculated in the speed controller cycle. This means that MD 1213, 1216 or 1219 must be smaller than the inverse value of two speed controller cycles MD 1001: $MD_SPEEDCTRL_CYCLE_TIME (speed controller cycle) (1/ 2*MD 1001 *31.25 microsec).

Clear alarm with the RESET key in all channels. Restart part program.


1-2645