Reactions:
Remedy:
Program Continuation:
Axis %1 drive %2 emergency retraction mode/generator mode not possible
%1 = NC axis number %2 = Drive number
Emergency retraction/Generator operation is only possible with an active DC link measurement (MD 1161: $MD_FIXED_LINK_VOLTAGE (DC link fixed voltage = 0). In an old hardware version, no DC link measurement is possible and therefore the error message 300765 might appear in addition if MD 1161: $MD_FIXED_LINK_VOLTAGE (DC link fixed voltage) is set to 0 in an old hardware version.
- NC not ready.
- The NC switches to follow-up mode.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
- Channel not ready.
Enter the value zero in the machine data MD 1161: $MD_FIXED_LINK_VOLTAGE (DC link fixed voltage), or order a new hardware version of the control module.
Clear alarm with the RESET key in all channels. Restart part program.
© Siemens AG 2005 All Rights Reserved