300764

Parameters:

Definitions:


Reactions:


Remedy:

Program Continuation:


Axis %1 drive %2 emergency retraction mode/generator mode not possible

%1 = NC axis number %2 = Drive number

Emergency retraction/Generator operation is only possible with an active DC link measurement (MD 1161: $MD_FIXED_LINK_VOLTAGE (DC link fixed voltage = 0). In an old hardware version, no DC link measurement is possible and therefore the error message 300765 might appear in addition if MD 1161: $MD_FIXED_LINK_VOLTAGE (DC link fixed voltage) is set to 0 in an old hardware version.

-    NC not ready.

-    The NC switches to follow-up mode.

-    Channel not ready.

-    NC Start disable in this channel.

-    Interface signals are set.

-    Alarm display.

-    NC Stop on alarm.

-    Channel not ready.

Enter the value zero in the machine data MD 1161: $MD_FIXED_LINK_VOLTAGE (DC link fixed voltage), or order a new hardware version of the control module.

Clear alarm with the RESET key in all channels. Restart part program.