300758

Parameters:

Definitions:


Reactions:


Remedy:


Program Continuation:


Axis %1 drive %2 generator mode: response voltage > switch-off threshold

%1 = NC axis number %2 = Drive number

The sum of the values in MD1631: $MD_LINK_VOLTAGE_GEN_ON (response voltage for generator axis) + MD1632: $MD_LINK_VOLTAGE_GEN_HYST (voltage range for generator control) is greater than MD1633: $MD_LINK_VOLTAGE_GEN_OFF (deactivation threshold for generator axis).

-    NC not ready.

-    The NC switches to follow-up mode.

-    Channel not ready.

-    NC Start disable in this channel.

-    Interface signals are set.

-    Alarm display.

-    NC Stop on alarm.

-    Channel not ready.

Please inform the authorized personnel/service department.

Modify drive machine data

Modify MD 1631: $MD_LINK_VOLTAGE_GEN_ON (response voltage for generator axis) or

Modify MD 1632: $MD_LINK_VOLTAGE_GEN_HYST (voltage range for generator control) or

Modify MD 1633: $MD_LINK_VOLTAGE_GEN_OFF (voltage range for generator control) or

Clear alarm with the RESET key in all channels. Restart part program.


1-2637