300734
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
1-2613
Axis %1 drive %2 zero load current less than or equal to zero
%1 = NC axis number %2 = Drive number
The value in MD 1136: $MD_MOTOR_NOLOAD_CURRENT (motor no-load current) is less than or equal to zero.
- NC not ready.
- The NC switches to follow-up mode.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
Please inform the authorized personnel/service department.
For standard motors: Reset the drive (delete the bootfile) and repeat the startup.
For third-party motors: Check and, if necessary, refer to the motor data sheet to correct MD 1136: $MD_MOTOR_NOLOAD_CURRENT (motor no-load current).
Switch control OFF - ON.