300728
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
1-2607
Axis %1 drive %2 adaption factor torque/current too high
%1 = NC axis number %2 = Drive number
The matching factor from setpoint torque to cross current in the speed controller is too large.
- NC not ready.
- The NC switches to follow-up mode.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
Please inform the authorized personnel/service department.
For standard motors: Reset the drive (delete the bootfile) and repeat the startup.
For third-party motors: Check and, if necessary, refer to the motor data sheet to correct MD 1103: $MD_MOTOR_NOMINAL_CURRENT (rated motor current) or MD 1107: $MD_INVERTER_MAX_CURRENT (transistor limit current) or MD 1113: $MD_TORQUE_CURRENT_RATIO (torque constant).
Switch control OFF - ON.