300712

Parameters:

Definitions:

Reactions:


Remedy:

Program Continuation:


Axis %1 drive %2 configuration of controller structure (higher dynamic response) not possible

%1 = NC axis number %2 = Drive number

On a 2-axis module, an attempt was made to change the control structure via MD 1004: $MD_CTRL_CONFIG in such a way that speed control would be performed in advance of current control. This is only allowed on 1-axis modules in order to improve the dynamic response!

-    NC not ready.

-    The NC switches to follow-up mode.

-    Channel not ready.

-    NC Start disable in this channel.

-    Interface signals are set.

-    Alarm display.

-    NC Stop on alarm.

Please inform the authorized personnel/service department. In the drive MD 1004: $MD_CTRL_CONFIG bit 2 must be set to zero (no) (default setting). This ensures that the current control acts before the speed control.

Switch control OFF - ON.


1-2591