Axis %1 drive %2 flux controller at limit
%1 = NC axis number %2 = Drive number
The specified flux setpoint cannot be achieved even though the maximum current has been provided.
Causes:
Incorrect motor data (replacement circuit diagram data)
Motor data and motor connection type (star/delta) do not match Motor has become unstable because motor data grossly wrong Current limit is too low for the motor (0.9 * MD 1238 * MD 1103 < MD 1136)
Power section too small
- Mode group not ready.
- The NC switches to follow-up mode.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
- Channel not ready.
Please inform the authorized personnel/service department. Remedy the cause.
Modify MD 1238: $MD_CURRENT_LIMIT (current limit)
Modify MD 1103: $MD_MOTOR_NOMINAL_CURRENT (motor nominal current)
Modify MD 1136: $MD_MOTOR_NOLOAD_CURRENT (motor no-load current)
Use greater power section.
Clear alarm with the RESET key in all channels of this mode group. Restart part program.