Configured positioning velocity is too high
When referencing, the spindle turned through a greater distance than given in the axis-specific machine data 34,060 REFP_MAX_MARKER_DIST, without receiving a reference mark signal.
The check is performed for spindle positioning with SPOS or SPOSA when the spindle has not previously run with speed control (S=...).
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
Check and correct the MD 34 060 REFP_MAX_MARKER_DIST.
The value entered states the distance in [mm] or [degrees] between 2 zero markers. Clear alarm with the RESET key. Restart part program