20147
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
1-1035
Channel %1 block %2 motion synchronous action: command not executable
%1 = Channel number %2 = Block number
One of the commands for the synchronous action block cannot be executed, e.g. it is not possible to perform a Reset to the synchronous action.
Measurement level 2
Embargo version does not allow measurement from a synchronized action MEASA was programmed in a synchronized action Measurement is already active Programming error (see alarm 21701)
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
Change synchronous action.
Measurement level 2
Execute the measurement task from an NC program first, in order to improve the error diagnostics. Only include it in the synchronized action when the first error-free run has been performed.
Clear alarm with the RESET key. Restart part program