18003

Parameters:

Definitions:

Reactions:

Remedy:

Program Continuation:

1-947

Channel %1 block %2 NCK protection zone %3 cannot be activated.Error code %4

%1 = Channel number %2 = Block number, label %3 = Number of channel-specific protection zone %4 = Error specification

An error has occurred on activating the protection zone. The error number gives the specific reason for the alarm.

The following meanings apply:

1: Incomplete or conflicting contour definition.

2: Contour encompasses more than one surface area.

3: Tool-related protection zone is not convex.

4: If both boundaries are active in the 3rd dimension of the protection zone and both limits have the same value.

5: The number of the protection zone does not exist (negative number, zero or greater than the maximum number of protection zones).

6: Protection zone definition consists of more than ten contour elements.

7: Tool-related protection zone is defined as inside protection zone.

8: Incorrect parameter used.

9: Protection zone to be activated is not defined or number of the contour element <2 or >MAXNUM_CONTOURNO_PROTECTAREA.

10: Error in internal structure of the protection zones.

11: Other errors not specified further.

12: The number of protection zones simultaneously active exceeds the maximum number (channel-specific machine data).

13,14: Contour element for protection zones cannot be created.

15,16: No more memory space for the protection zones.

17: No more memory space for the contour elements.

-    Correction block is reorganized.

-    Interface signals are set.

-    Alarm display.

If the alarm is output on ramp-up (2nd parameter: "INIT" instead of block number),

"Channel not ready to operate" will be set

Please inform authorized personnel / the service department.

1.    Reduce the number of simultaneously active protection zones (MD).

2.    Modify part program:

Delete other protection zones.

Preprocessing stop.

When the alarm occurs on control ramp-up, system variables $SC_PA_... must be corrected for the specified protection zone. Afterwards perform a restart. If the erroneous data cannot be recognized, the protection zone's immediate activation can be removed and the system variables of the protection zone can be written again by means of CPROTDEF.

Clear alarm with NC START or RESET key and continue the program.

If the alarm occurs during NC program execution, the current block can be changed. This way, also the CPROT parameters can be adjusted. However, if there is an error in the definition of the protection zone, the NC program must be aborted and the definition must be corrected under CPROTDEF.

If the alarm occurs on control ramp-up, system variables $SC_PA_... must be corrected for the specified protection zone. This can be done by downloading an Initial.ini file that