15910

Parameters:

Definitions:


Reactions:


Remedy:

Program Continuation:


Channel %1 block %2 touch probe not allowed

%1 = Channel number

%2 = Block number, label

Measure without deletion of distance-to-go

In the part program, an illegal probe has been programmed with the command MEAW (measure without distance-to-go). The probe numbers

0    ... no probe

1    ... probe 1

2    ... probe 2

are allowed, whether the probe is actually connected or not.

Example:

N10 MEAW=2 G01 X100 Y200 Z300 F1000 Probe 2 without deletion of distance-to-go

-    Correction block is reorganized.

-    Interface signals are set.

-    Alarm display.

Include a probe number within the limits given above in the keyword MEAW=... This must correspond to the hardware connection of the probe.

Clear alarm with NC START or RESET key and continue the program.