15900

Parameters:

Definitions:


Reactions:


Remedy:

Program Continuation:


Channel %1 block %2 touch probe not allowed

%1 = Channel number

%2 = Block number, label

Measure with deletion of distance-to-go

In the part program, an illegal probe has been programmed with the command MEAS (measure with deletion of distance-to-go). The probe numbers

0    ... no probe

1    ... probe 1

2    ... probe 2

are allowed, whether the probe is actually connected or not.

Example:

N10 MEAS=2 G01 X100 Y200 Z300 F1000 Probe 2 with deletion of distance-to-go

-    Correction block is reorganized.

-    Interface signals are set.

-    Alarm display.

Include a probe number within the limits given above in the keyword MEAS=... This must correspond to the hardware connection of the probe.

Clear alarm with NC START or RESET key and continue the program.


1-749