15110

Channel %1 block %2 REORG not possible

Parameters:

%1 = Channel number

%2 = Block number, label

Definitions:

In order to synchronize the preprocessing run and the main run with REORG, the control accesses modification data which are maintained in a logfile. The alarm indicates that no more capacity is available in the logfile for the specified block in the channel.

The alarm message means that the logfile has been deleted in order to obtain additional memory for program reorganization. Consequently, it is no longer possible to REORG the preprocessing memory up to the next coincidence point.

Reactions:

Remedy:

- Alarm display.

Please inform the authorized personnel/service department. No remedial measures are available for the further execution of the current part program, however:

1.    Reduce log file size requirement by:

Reducing the distance between the preprocessing and the main run via appropriate

preprocessing

stops STOPRE.

2.    Increase the size of the logfile by means of the channel-specific machine data:

Modify MD 28000: MM_REORG_LOG_FILE_MEM and

Modify MD 28010: MM_REORG_LUD_MODULES

Program Continuation:

Alarm display showing cause of alarm disappears. No further operator action necessary.