12100

Parameters:


Definitions:


Reactions:


Remedy:


Program Continuation:


Channel %1 block %2 number of passes %3 not permissible

%1 = Channel number %2 = Block number, label %3 = Number of passes

The subroutines called with MCALL are modal, i.e. after each block with positional information a routine run is automatically performed once. For this reason, programming of the number of passes under address P is not allowed.

The modal call is effective until another MCALL is programmed, either with a new subroutine name or without (delete function).

-    Correction block

-    Interface signals are set.

-    Alarm display.

Press the NC Stop key and select the function "Correction block" with the softkey PROGRAM CORRECT. The correction pointer positions on the incorrect block.

Program the subroutine call MCALL without number of passes.

Clear alarm with NC START or RESET key and continue the program.