In case of alarms the 8B30motor temperature is too high, 8BB0 motor temperature low, etc. you can temporarily disable the alarms in parameter 2220.Temperature too low -bit 5.too low -bit 4
Physically check that the temperature is OK before making changes.(the problem is with temperature sensor)This is only a temporary solution (motor, cable, module need to be repaired).
You can also block other faults here. Bit 7 input frequency encoder ( 8860 Input frequency of speed encoder %.2s , 8C60 Signal frequency at encoder of speed input %.2s etc.)
MP2220 Monitoring functions
;Input: %xxxxxxxxxxxxxxxx
;Bit 0 Reference-mark monitoring
; 0 = Active
; 1 = Not active
;Bit 1 Monitoring of rotational direction
; 0 = Active
; 1 = Not active
;Bit 2 Power limiting of the spindle for -ERR.IZ.GR
; (only for HEIDENHAIN inverters except UE 2xx)
; 0 = Active
; 1 = Not active
;Bit 3 Vibrations are suppressed during switch-off of
; drive
; 0 = Active
; 1 = Not active
;Bit 4 only CC 424, CC 61xx:
; Monitoring temperature too high
; 0 = Active
; 1 = Not active
;Bit 5 only CC 424, CC 61xx:
; Monitoring temperature too low
; 0 = Active
; 1 = Not active
;Bit 6 reserved
;Bit 7 CC 422: reserved
;Bit 7 only CC 424, CC 61xx:
; Monitoring input frequency encoder
; 0 = Active
; 1 = Not active
;Bit 8 only CC 424, CC 61xx:
; Compensating the mechanical offset
; by a step by step increasing of the kV
; 0 = Active
; 1 = Not active